| pecifications |   | 
| MODEL | dlt: | |  DLT 3100 | DLT 3120 | DLT 3160 | DLT 3200 | DLT 3250 | DLT 3300 |  
  | 
| Power | |  100 kVA |  120 kVA | 160 kVA | 200 kVA | 250 kVA | 300 kVA |  
  | 
| INPUT |   | 
| Voltage | 220 / 400 Vac 3 Phase +N, +/-% 15 | 
| By-Pass Voltage | 220 / 400 Vac 3 Phase +N, +/-% 10 | 
| Input Frequency | 50 Hz, +/- %5 | 
| EMI | EN50091 -2 Class A | 
| Input out of Tolerant Protection | Electronic input out of tolerant protection | 
| OUTPUT |   | 
| Power (kW) |  | 
| Power Factor | 0,8 | 
| Voltage | 220/400 Vac 3 Phase+N | 
| Frequency | 50 Hz. (60Hz On Request) | 
| Frequency Tolerance | +1-2% (Line Synchronized) • +/-0,2% (Free Running) | 
| Efficieny at 100% Load | %90-92 | 
| Crest Factor | 3:1 | 
| Overload Protection | | 100 % 125% Load : 10 min | • 125 % 150% Load : 1 min |  • <150% Load : By-Pass |  
  | 
| Short Circuit Protection | Electrolnc short circuit protection | 
| Tfahage out of ldemt Protection | Electronic out of tolerant protection | 
| Total Harmonic Distortion | <3% | 
| THD | Non Linear Load <%5 | 
| BATTERIES |   | 
| Battery Type | Sealed Lead Acid – Maintenance Free | 
| Number of Batteries |  | 
| Float Charging Voltage |  | 
| End of Discharge Voltage |  | 
| Ambient Temperature c | 25 c° | 
| Battery Voltage Protection | Electronic Battery out of tolerant protection | 
| Battery Protection | Automatic circuit breaker | 
| Battery Test | Automatic every 72 hours | 
| GENERAL |   | 
| Communication | RS232 + Dry Contacts | 
| Temperature Range | 0C° – 40 c° | 
| Humidity (Non Condensed) | 90 % (Non condensed) | 
| Protection Degree | IP20 | 
| Altitude | < 1000 m. above sea level | 
| Noise level | < 65 dBA < 70 dBA | 
| Weight without batteries (kg) | 750 765 810 970 1330 1370 | 
| Dimensions (mm) HxWxD | 1650x1100x800 1730x1195x870 1880x1565x925 | 
| Ventilation | Forced air cooling. | 
| OPTIONS |  | 
| Input Transformers | |   Galvanic Isolation transformer at the Input (In the external cabinet) | Monitoring and Control Software |  T-MON 3 client standart |  
  | 
| Input THD | |  <10%(with 18 Pulse Rectifier .according to UPS range |  Multiserver Shutdown Unit |  Available as option |  
  | 
|   5% (with 18 Pulse rectifier, + filter) upto 80 kVA | SNMP CommunknlianAdaptor |  Available as option |  
  | 
| Parallel Operation | |  1+3 Systems (N+1 redundant, reduntant, symetrlc parallel) | Serial Port Enhancer |  Available as option |  
  | 
| MBS | |  Maiitenanoe by-pass switch for complete isolation (For2062Ơ7&210) | MorDusCommutioriion Adaptor |  Available as option (over RS485 or over TCP/IP) |  
  |